<law><site_title>Virginia Decoded</site_title><site_url>https://vacode.org</site_url><law_id>364479</law_id><section_number>45.2-807</section_number><catch_line> Power circuits</catch_line><edition url="https://vacode.org/2026/" slug="2026" current="TRUE" last_updated="2026-08-02">2026</edition><structure><unit label="title" level="1" order_by="99" identifier="45.2">Mines, Minerals, and Energy</unit><unit label="subtitle" level="2" order_by="2" identifier="II">Coal Mining</unit><unit label="part" level="3" order_by="2" identifier="B">Underground Coal Mines</unit><unit label="chapter" level="4" order_by="2" identifier="8">Requirements Applicable to Underground Coal Mines; Electricity, Safety, Etc</unit><unit label="article" level="5" order_by="2" identifier="2">Electricity</unit></structure><text>
						<section id="A"><p><span class="prefix-number">A.</span> All underground power wires and cables shall (i) have adequate current-carrying capacity, (ii) be guarded from mechanical injury, and (iii) be installed in a permanent manner. <a id="paragraph-1357860" class="section-permalink" href="https://vacode.org/45.2-807/#A"><i class="fa fa-link"/></a></p></section>
						<section id="B"><p><span class="prefix-number">B.</span> Wires and cables that are not encased in armor shall be supported by well-installed insulators and shall not touch any roof, rib, or combustible <span class="dictionary">material</span>; however, this prohibition shall not apply to ground wires, grounded power conductors, or trailing cables. <a id="paragraph-1357861" class="section-permalink" href="https://vacode.org/45.2-807/#B"><i class="fa fa-link"/></a></p></section>
						<section id="C"><p><span class="prefix-number">C.</span> Power wires or cables that are installed in a belt-haulage slope shall be insulated adequately and buried in a trench at least one foot below any combustible <span class="dictionary">material</span>, unless such wires or cables are encased in armor or otherwise fully protected against mechanical injury. <a id="paragraph-1357862" class="section-permalink" href="https://vacode.org/45.2-807/#C"><i class="fa fa-link"/></a></p></section>
						<section id="D"><p><span class="prefix-number">D.</span> Any splice or repair in a power cable shall: <a id="paragraph-1357863" class="section-permalink" href="https://vacode.org/45.2-807/#D"><i class="fa fa-link"/></a></p></section>
						<section id="D1" class="indent-1"><p><span class="prefix-number">1.</span> Be mechanically strong and have adequate electrical conductivity; <a id="paragraph-1357864" class="section-permalink" href="https://vacode.org/45.2-807/#D1"><i class="fa fa-link"/></a></p></section>
						<section id="D2" class="indent-1"><p><span class="prefix-number">2.</span> Be effectively insulated and <span class="dictionary">sealed</span> so as to exclude moisture; <a id="paragraph-1357865" class="section-permalink" href="https://vacode.org/45.2-807/#D2"><i class="fa fa-link"/></a></p></section>
						<section id="D3" class="indent-1"><p><span class="prefix-number">3.</span> If the cable has metallic armor, possess mechanical protection and electrical conductivity equivalent to that of the original armor; and <a id="paragraph-1357866" class="section-permalink" href="https://vacode.org/45.2-807/#D3"><i class="fa fa-link"/></a></p></section>
						<section id="D4" class="indent-1"><p><span class="prefix-number">4.</span> If the cable has metallic shielding around each conductor, possess new shielding that is equivalent to the original shielding. <a id="paragraph-1357867" class="section-permalink" href="https://vacode.org/45.2-807/#D4"><i class="fa fa-link"/></a></p></section>
						<section id="E"><p><span class="prefix-number">E.</span> Every underground high-voltage transmission cable shall be: <a id="paragraph-1357868" class="section-permalink" href="https://vacode.org/45.2-807/#E"><i class="fa fa-link"/></a></p></section>
						<section id="E1" class="indent-1"><p><span class="prefix-number">1.</span> Installed only in a regularly inspected airway; <a id="paragraph-1357869" class="section-permalink" href="https://vacode.org/45.2-807/#E1"><i class="fa fa-link"/></a></p></section>
						<section id="E2" class="indent-1"><p><span class="prefix-number">2.</span> Covered, buried, or placed on insulators so as to afford protection against damage by derailed equipment if it is installed along a haulage road; <a id="paragraph-1357870" class="section-permalink" href="https://vacode.org/45.2-807/#E2"><i class="fa fa-link"/></a></p></section>
						<section id="E3" class="indent-1"><p><span class="prefix-number">3.</span> Guarded if miners regularly work or pass under such cable, unless it is at least 6.5 feet above the floor or rail; <a id="paragraph-1357871" class="section-permalink" href="https://vacode.org/45.2-807/#E3"><i class="fa fa-link"/></a></p></section>
						<section id="E4" class="indent-1"><p><span class="prefix-number">4.</span> Securely anchored, properly insulated, and guarded at its ends; and <a id="paragraph-1357872" class="section-permalink" href="https://vacode.org/45.2-807/#E4"><i class="fa fa-link"/></a></p></section>
						<section id="E5" class="indent-1"><p><span class="prefix-number">5.</span> Covered, insulated, or placed to prevent contact with any trolley <span class="dictionary">circuit</span> or other low-voltage <span class="dictionary">circuit</span>. <a id="paragraph-1357873" class="section-permalink" href="https://vacode.org/45.2-807/#E5"><i class="fa fa-link"/></a></p></section>
						<section id="F"><p><span class="prefix-number">F.</span> Any new high-voltage disconnect that is installed on underground electrical equipment shall automatically ground all three power leads when in the open position. Every high-voltage disconnect that is rebuilt or remanufactured after July 1, 2011, shall meet this standard. <a id="paragraph-1357874" class="section-permalink" href="https://vacode.org/45.2-807/#F"><i class="fa fa-link"/></a></p></section>
						<section id="G"><p><span class="prefix-number">G.</span> Every power wire or cable shall be insulated adequately where it passes into or out of an electrical compartment and where it passes through a door or stopping. <a id="paragraph-1357875" class="section-permalink" href="https://vacode.org/45.2-807/#G"><i class="fa fa-link"/></a></p></section>
						<section id="H"><p><span class="prefix-number">H.</span> Where track is used as a power conductor: <a id="paragraph-1357876" class="section-permalink" href="https://vacode.org/45.2-807/#H"><i class="fa fa-link"/></a></p></section>
						<section id="H1" class="indent-1"><p><span class="prefix-number">1.</span> Both rails of main-line tracks shall be welded or bonded at every joint, and cross <span class="dictionary">bonds</span> shall be installed at intervals of not more than 200 feet. If the rails are paralleled with a feeder <span class="dictionary">circuit</span> of like polarity, such paralleled feeder shall be bonded to the track rails at intervals of not more than 1,000 feet; <a id="paragraph-1357877" class="section-permalink" href="https://vacode.org/45.2-807/#H1"><i class="fa fa-link"/></a></p></section>
						<section id="H2" class="indent-1"><p><span class="prefix-number">2.</span> At least one rail on any secondary track-haulage road shall be welded or bonded at every joint, and cross <span class="dictionary">bonds</span> shall be installed at intervals of not more than 200 feet; and <a id="paragraph-1357878" class="section-permalink" href="https://vacode.org/45.2-807/#H2"><i class="fa fa-link"/></a></p></section>
						<section id="H3" class="indent-1"><p><span class="prefix-number">3.</span> Track switches on entries shall be well bonded. <a id="paragraph-1357879" class="section-permalink" href="https://vacode.org/45.2-807/#H3"><i class="fa fa-link"/></a></p></section></text><history>Code 1950, &#xA7;&#xA7; 45-82, 45-82.1; 1954, c. 191; 1966, c. 594, &#xA7; 45.1-78; 1993, c. 442; 1994, c. 28, &#xA7; 45.1-161.186; 1996, c. 774; 1999, c. 256; 2005, c. 3; 2011, cc. 826, 862; 2021, Sp. Sess. I, c. 387.</history><metadata></metadata></law>